Automated assessment of short-circuit currents in 0.4 kV rural networks to improve power supply reliability of agricultural facilities
DOI:
https://doi.org/10.53083/1996-4277-2026-265-11-86-96Keywords:
power supply reliability, electrical equipment operation, electrical network, agricultural power supply, short circuit, phase-zero loop, 10/0.4 kV transformer, protective equipmentAbstract
An improved computational software method for assessing short-circuit currents in 0.4 kV rural electric networks is proposed. The method is focused on extended lines supplying agricultural facilities and differs from a standard tabular calculation by separate consideration of phase and neutral conductor resistances, the phase-to-neutral loop impedance, fault contact resistance and the influence of input-data uncertainty on the final current values. The software implementation was developed in Python and included calculation of 10/0.4 kV transformer parameters, line impedances, three-phase short-circuit current, peak current and single-phase short-circuit current. Verification was carried out for three network variants with 100, 250 and 630 kV·A transformers, different line lengths and conductor cross-sections. For the reference variant with a 250 kV·A transformer and a 0.300 km line, the obtained values were: three-phase short-circuit current 0.890 kA, peak current 1.511 kA and single-phase short-circuit current 0.368 kA. It was found that a contact resistance of 0.0001 kOhm reduced the calculated single-phase short-circuit current to 0.318 kA, i.e. by 13.7%. The parametric analysis showed that when the line length increased from 0.050 to 0.500 km, the single-phase short-circuit current decreased from 1.208 to 0.237 kA. The developed algorithm may be used for design, reconstruction and operational assessment of power supply networks for agricultural facilities.